Impact Analysis of midpoint Connected STATCOM on Distance Relay Performance

Indonesian Journal of Electrical Engineering and Computer Science

Impact Analysis of midpoint Connected STATCOM on Distance Relay Performance

Abstract

This paper presents the impact of the Static Synchronous Compensator (STATCOM) on the performance of distance protection of EHV transmission lines. A 400kV transmission system having midpoint connected STATCOM with its control circuit is modeled using MATLAB/SIMULINK software. The impact of STATCOM on distance relay for different fault conditions and different fault locations is analyzed. Simulation results indicate that the presence of the STATCOM in the transmission system significantly changes the line impedance seen by the distance relay to be lower or higher than the actual line impedance. Due to this the performance of the distance relay changes, either overreaches or under reaches. DOI: http://dx.doi.org/10.11591/telkomnika.v13i2.6987 

Discover Our Library

Embark on a journey through our expansive collection of articles and let curiosity lead your path to innovation.

Explore Now
Library 3D Ilustration